| Generating set general Model | 120GFT | |
| Structure | integral | |
| Exciting method | AVR Brushless | |
| Rated Power (kW) | 120 | |
| Rated Current(A) | 217 | |
| Rated Voltage(V) | 400/230 | |
| Rated Frequency(Hz) | 50 | |
| Rated Power Factor | 0.8 LAG | |
| No load voltage setting range | 95%-105% | |
| Steady state voltage regulation rate | ≤±1% | |
| Transient state voltage regulation rate | ≤-15%—+20% | |
| Voltage fluctuation rate | ≤3s | |
| Steady state frequency regulation rate | ≤±0.5% | |
| Transient state frequency regulation rate | ≤±10% | |
| Frequency stabilization time | ≤5s | |
| Line-voltage waveform sinusoidal distortion rate | ≤2.5% | |
| Gas Engine | Model | ND119D14 |
| Type | In line, 4 strokes, electric control ignition, pre-mixed stoichiometry burn | |
| Cylinder number | 6 | |
| Bore x Stroke (mm) | 132X145 | |
| Total displacement (L) | 11.9 | |
| Rated Power (kW) | 140 | |
| Rated Speed (r/min) | 1500/1800 | |
| Speed Regulation Mode | Electrical | |
| Starting Mode | Electrical | |
| Fuel type | Natural gas/biogas | |
| Overall dimension (L x W x H)(mm) | 2450X1250X1750 | |
| Net weight (kg) | 1680 | |